The Cyrix-Li-Charge will connect a battery charger with 3 seconds delay:
– if the Charge Disconnect output of the VE.Bus BMS is high, and – if it senses 13,7V (resp. 27,4V or 54,8V) or more on its battery charger connection terminal, and – if it senses 2V or more on its battery terminal (the Cyrix will remain open, if not connect to the battery).
The Cyrix-Li-Charge will disengage immediately whenever its control input becomes free floating, signalling cell over voltage or cell over temperature.
In general a cell over voltage alarm will reset shortly after charging has been stopped. The Cyrix will then reconnect the charger after a delay of 3 seconds. After two attempts to reengage with 3 seconds delay, the delay increases to 10 minutes.